Cable Fault Location & Testing Equipments for Low, Medium and High Voltage Networks

Products: DC HV Test Sets: PGT 25-D1.5

The PGT 25-D1.5 is a cable testing device for VDE-compliant DC voltage testing of cables and cable systems (for testing the cable insulation of a newly laid cable before commissioning, in compliance with VDE 0276-620/621).

Thanks to its compact dimensions and less weight, this device is portable and can be used directly on site.

The readable values of output voltage and leakage current make it possible to evaluate the state of the test object as regards voltage stability and insulation capacity.

 

CHARACTERISTICS

PGT 25-D1.5  
Output voltage 0 to 25 kV (negative polarity)
Output current 1.5 mA
Short circuit current 1.6 mA
Discharge energy 3000 J (internal discharge device)
Power Supply

230 V ± 10 %, 50 Hz

Internal rechargeable battery

 

Products: DC HV Test Sets: PGT 50-D6

The PGT DC test sets comprise an operating and a high voltage component. They are used for VDE-compliant DC voltage testing of cables and cable systems (for testing the cable insulation of a newly laid cable before commissioning, in compliance with VDE 0276-620/621).

Thanks to their compact dimensions and less weight, these sets are portable and can be used directly on site.

The readable values of output voltage and leakage current make it possible to evaluate the state of the test object as regards voltage stability and insulation capacity.

 

CHARACTERISTICS

PGT 50-D6  
Output voltage 0 to 50 kV (negative polarity)
Output current 6 mA
Over current release > 8 mA
Discharge energy 6 μF (internal discharge device)
Power Supply

230 V ± 10 %, 50 Hz

 

 

 

Products: DC HV Test Sets: PGT 80-D5

The PGT DC test sets comprise an operating and a high voltage component. They are used for VDE-compliant DC voltage testing of cables and cable systems (for testing the cable insulation of a newly laid cable before commissioning, in compliance with VDE 0276-620/621).

Thanks to their compact dimensions and less weight, these sets are portable and can be used directly on site.

The readable values of output voltage and leakage current make it possible to evaluate the state of the test object as regards voltage stability and insulation capacity.

 

CHARACTERISTICS

PGT 80-D5  
Output voltage 0 to 80 kV (negative polarity)
Output current 5 mA
Over current release > 7 mA
Discharge energy 4 μF (internal discharge device)
Power Supply

230 V ± 10 %, 50 Hz

 

 

 

Products: DC HV Test Sets: PGT 110-D4

The PGT DC test sets comprise an operating and a high voltage component. They are used for VDE-compliant DC voltage testing of cables and cable systems (for testing the cable insulation of a newly laid cable before commissioning, in compliance with VDE 0276-620/621).

Thanks to their compact dimensions and less weight, these sets are portable and can be used directly on site.

The readable values of output voltage and leakage current make it possible to evaluate the state of the test object as regards voltage stability and insulation capacity.

 

CHARACTERISTICS

PGT 110-D4  
Output voltage 0 to 110 kV (negative polarity)
Output current 3.5 mA
Over current release > 5.5 mA
Discharge energy 22 μF (internal discharge device)
Power Supply

230 V ± 10 %, 50 Hz

 
 

 

    

 

Home      Products      Testing Services      Technical Topics      Contact_UsEnglish

 

All right reserved

www.technopowereg.com

        

Electrical Test Equipment For Substation and Protection Relay Testing

 
Cable Fault Location and Testing Equipments for Low, Medium and High Voltage Networks
  TDR Device
  Cable Fault Location
  Pin-Pointing Device

  Line Tracing Sets

  DC HV Test Sets

    ◾ PGT 25-D1.5
    ◾ PGT 50-D6
    ◾ PGT 80-D5
    ◾ PGT 110-D4

  Cable Identification Set

 
Non contact temperature measurement

 

 

 

 

 

DC HV Test Sets Applications:

DC voltage testing of cables and cable systems (for testing the cable insulation of a newly laid cable before commissioning

 

 

 

 

PGT_25 datasheet

PGT_50-110 datasheet