Electrical Test Equipment For Substation & Protection Relay Testing
Products: Primary Injection: Raptor
Multifunction Primary Testing System
The Raptor is a smart test set designed as the definitive solution for the main primary test applications required in the commissioning and maintenance of substations.
This new generation of Primary Injection Test System makes primary testing easier, faster and more convenient.
Raptor System | Max. (A) Permanent | Max. (A) 3 minutes | Max. (A) 3 seconds |
Raptor C-05 | 3800 A / 3 kVA | 7500 A / 3 kVA | 9500 A / 2.55 kVA |
Raptor C-15 | 3800 A / 8.2 kVA | 7500 A / 11.5 kVA | 15000 A / 3.9 kVA |
Raptor C-25 | 3800 A / 13.3 kVA | 7500 A / 19.7 kVA | 15000 A / 13 kVA |
Raptor C-35 | 3800 A / 18.4 kVA | 7500 A / 28 kVA | 15000 A / 22 kVA |
Raptor C-05
his configuration is for applications where the High Current injection is required to work close to the load, such as CT, VT, PT, polarity, load saturation and relay timing test, among others. The Raptor has the ability to work at different frequencies, even with the high current output, from 20 to 400 Hz, making it adequate for testing low level signals, free of the noise and interferences generated at the network fundamental frequency.
The configuration includes:
1 Master unit.
1 Control interface Raptor HH.
1 Set of standard accessories.
Raptor C-15
This configuration is for applications where the High Current injection values require more power (compliance voltage) to reach the desired current in the test object using either lower cross section cables, which are easier to handle, or longer higher cross section cables to increase the distance to the object under test. The Raptor Slave unit has twice the power of the Master unit.
The configuration includes:
1 master unit.
1 slave unit.
1 Control interface Raptor HH.
1 Set of standard accessories.
Raptor C-25
This configuration is for applications where the High Current injection values are high enough to require more power (compliance voltage) to reach the desired current in the test object, which usually requires long cables. Using this configuration instead of the C-15 will avoid the need to wind turns on it to be able to reach a distant load, achieving higher currents. This configuration is adequate for injection of high current levels (>4000 A) into loads situated at a typical distance (around 3 meters) of the test set, using of course, cables with the required cross section.
The configuration includes:
1 master unit.
2 slave units.
1 Control interface Raptor HH.
1 Set of standard accessories.
Raptor C-35
This configuration is for applications where the High Current injection values are high enough to require even more power (compliance voltage) to reach the desired current in the test object, which usually requires long cables. Using this configuration instead of the C-25 will avoid the need to wind turns on it to be able to reach a distant load, achieving higher currents. Each RAPTOR SL unit added to the system makes for almost twice the power of the MASTER. This configuration is sufficient adequate for injection of very high current levels (>8000 A) into loads situated close in distance (around 1 meter) of the test set, using of course, cables with the required cross section. Low voltage CB up to a nominal of 1500 A can be properly tested.
The configuration includes:
1 master unit.
3 slave units.
1 Control interface Raptor HH.
1 Set of standard accessories.
All right reserved
www.technopowereg.com
Raptor Applications:
Primary current injection testing.
Current Transformer testing.
CT Magnetization Curve and Knee Point
Polarity Testing of the PT, CT and VT.
Circuit Breaker testing.
Recloser and Sectionalizers.
Switchgear Testing.
Heat runs.
Ground Grid testing.
Protection Relay testing.